MLC Centre
Overview
Floor Profile
a) Floor to ceiling height 2640mm
b) Core to window span 10.6m
c) Ceiling grid 1,200mm
d) Slab to soffit 3,300mm
Air Conditioning
a) Centre zone Variable volume (VAV)
b) Perimeter zone Induction units
c) Number of zones per floor 42 standard, expandable to 66
(d) Design capacity i) People 1 person/10m2
  ii) Lighting (w/m2) 15
  iii) Tenant Equipment (w/m2) 20
e) Floor by floor capacity after hours Yes
f) Dedicated Condenser Water Capacity (w/m2) 38
g) Ancillary exhaust 300l/s max per floor
h) Ancillary fresh air 300l/s max per floor
Lifts
a) Type Gearless Traction
b) Number/Speed Low Rise 6 @ 3.5m/s
  Mid Rise 6 @ 5.0m/s
  High Rise 6 @ 6.0m/s
  Sky Rise 6 @ 7.0m/s
c) Capacity (passenger) 1564kg/1364kg
d) Goods Lifts/Speed 1 @ 2.5m/s
e) Capacity (goods) 1635kg
f) Standby Goods Lift Yes
Artificial Lighting
a) Average in open office areas 600 lux
Security
a) Security desk in lobby staffed 24 hours/7 days Yes
b) Concierge desk staffed 8.00am to 6.00pm 5 days Yes
c) Proximity access control Yes
d) Surveillance camera monitoring of lifts, public areas, and car park Yes
Power Reticulation
a) Power into building 3 substations 11kv triple grid
b) Service duct capacity Yes
c) Reticulation around floors 3 channel perimeter ducting
d) Emergency power Diesel generators serving essential standby and tenant services
e) Submains to office floors 80VA/m2 to a maximum of 120VA/m2
Communications
a) Number of telephone lines per floor 200
b) Dedicated tenant riser space Extensive
c) Reticulation around floors Dedicated communication cable trays and catenary wires extending from service corridor to perimeter of floor
d) Satellite capability Yes
e) Microwave capability Yes
f) Fibre optic capability Yes